Soft starter

  • Full load
  • Set the motor protection to the rated current according to the rating plate.
  • Partial load operation
  • Set the motor protection to 5 % above the current measured at the duty point.

Please observe the following points:

  • Current consumption must always be below the rated current.
  • Complete starting and stopping within 30 s.
  • To avoid power dissipation, bypass the electronic starter (soft start) once normal operation is reached.